(N) Operation via communication and its settings
Parameters
5 - 488
5.12.6
MODBUS® RTU communication specification
Operation by MODBUS® RTU communication or parameter setting is possible by using the MODBUS®
RTU communication protocol from the RS-485 terminals of the inverter.
Pr.
Name
Initial
value
Setting
range
Description
331
N030
RS-485 communication
station number
0
0
Broadcast communication
1 to 247
Inverter station number specification
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
332
N031
RS-485 communication
speed
96
3, 6, 12, 24,
48, 96, 192,
384, 576,
768, 1152
Set the communication speed.
The setting value × 100 equals the communication
speed.
For example, if 96 is set, the communication speed is
9600 bps.
334
N034
RS-485 communication
parity check selection
2
0
Without parity check
Stop bit length 2 bits
1
With parity check at odd numbers
Stop bit length 1 bit
2
With parity check at even numbers
Stop bit length 1 bit
343
N080
Communication error
count
0
⎯
Displays the communication error count during
MODBUS® RTU communication. Read-only.
539
N002
MODBUS® RTU
communication check
time interval
9999
0
MODBUS® RTU communication, but the inverter trips
in the NET operation mode.
0.1 to 999.8 s
Set the interval of the communication check (signal
loss detection) time. (same specifications as Pr. 122)
9999
No communication check (signal loss detection)
549
N000
Protocol selection
0
0
Mitsubishi inverter protocol (computer link)
1
MODBUS® RTU protocol
2
BACnet MS/TP protocol
NOTES
To use the MODBUS® RTU protocol, set "1" to Pr. 549 "Protocol selection".
If MODBUS® RTU communication is performed from the master to the address 0 (station number
0), the data is broadcasted, and the inverter does not send any reply to the master. To obtain
replies from the inverter, set Pr. 331 "RS-485 communication station number"
≠
"0 (initial value)".
Some functions are disabled in broadcast communication. (Refer to page 5-491.)
If a communication option is mounted with Pr. 550 "NET mode operation command source selec-
tion" = "9999 (initial value)", commands (operation commands) transmitted via RS-485 terminals
become invalid. (Refer to page 5-130.)
Upon delivery the FR-F800-E inverter models are not equipped with the RS-485 terminal block.
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......