Connection of stand-alone option units
Installation and wiring
2 - 78
2.8.5
Connection of the power regeneration common converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the inverter terminals
(P/+, N/-) and the power regeneration common converter (FR-CV) terminals as shown below so that
their symbols match with each other.
The FR-CV is applicable to the FR-F820-02330(55K) or lower and the FR-F840-01160(55K) or lower.
After making sure that the wiring is correct, set "2" in Pr. 30 "Regenerative function selection". (Refer
to page 5-552.)
Remove jumpers between terminals R/L1 and R1/L11 as well as between S/L2 and S1/L21, and
connect the power supply for the control circuit to terminals R1/L11 and S1/L21. Do not connect
anything to power input terminals (R/L1, S/L2, T/L3). Incorrect connection will damage the inverter.
E.OPT (option fault) will occur. (Refer to page 6-25.)
Do not insert an MCCB between terminals P/+ and N/- (between terminals P/L+ and P/+ or
between N/L- and N/-). Connecting the opposite polarity of terminals N/- and P/+ will damage the
inverter.
Use Pr. 178 to Pr. 189 (input terminal function selection) to assign the terminals used for the X10
signal. (Refer to page 5-285.)
Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter
without connecting them will damage the power regeneration common converter.
!
Always connect terminal RDYB of the FR-CV to the inverter terminal where the X10 signal or the
MRS signal is assigned to. Always connect terminal SE of the FR-CV to the inverter terminal SD. Not
connecting these terminals may damage the FR-CV.
I001039E
Fig. 2-54:
Connection of the power regeneration common converter (FR-CV)
NOTES
The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1,
S2/L2, and T2/L3 must be matched.
Use the sink logic (factory setting) when the FR-CV is connected. It cannot be connected when the
source logic is selected.
Do not connect a DC reactor (FR-HEL) to the inverter when FR-CV is connected.
M
3~
Three-
phase AC
power
supply
!
Inverter
Dedicated stand-alone
reactor (FR-CVL)
FR-CV type
Power regeneration common
converter
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......