![Mitsubishi Electric FR-F820-00046 Скачать руководство пользователя страница 722](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886722.webp)
(G) Control parameters
Parameters
5 - 550
5.13.9 Stop
selection
Select the stopping method (deceleration to stop or coasting) at turn-OFF of the start signal.
Use this function to stop a motor with a mechanical brake at turn-OFF of the start signal.
Selection of start signal (STF/STR) operation can also be selected. (For start signal selection, refer to
page 5-293.)
Make the motor perform deceleration stop
●
Set Pr. 250 = "9999 (initial value) or 8888".
●
It will perform deceleration stop when the start signal (STF/STR) is turned OFF.
Parameters referred to
Pr. 10
DC injection brake operation frequency
=>
Pr. 11
DC injection brake operation time
=>
Pr. 12
DC injection brake operation voltage
=>
Pr. 13
Starting frequency
=>
Pr.
Name
Initial
value
Setting
range
Description
Start signal (STF/STR)
(Refer to page 5-293.)
Stop operation
250
G106
Stop selection
9999
0 to 100 s
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
It will coast to stop after
set time when the start
signal is turned OFF.
1000 s to
1100 s
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
It will coast to stop after
(Pr. 250 – 1000) s when the
start signal is turned OFF.
9999
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
It will perform
deceleration stop when
the start signal is turned
OFF.
8888
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
I001143E
Fig. 5-268:
Stop operation when parameter 250 = 8888 or 9999
Output
frequency [Hz]
Start signal
DC brake
Deceleration starts when start signal turns off
Time
ON
ON
OFF
OFF
RUN signal
Deceleration time (Time set in Pr. 8, etc.)
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......