(H) Protective function parameter
Parameters
5 - 174
Operation of protective functions during emergency drive
●
Operation of protective functions during emergency drive is as follows.
While the switchover to the commercial power supply operation during emergency drive opera-
tion is enabled, when the same protective function is activated twice consecutively, the retry is
attempted up to twice.
●
The fault output during emergency drive operation is as follows.
Input signal operation
●
During emergency drive operation in the fixed frequency mode or in the PID control mode, input
signals unrelated to the emergency drive become invalid with some exceptions.
●
The table below shows functions of the signals that do not become invalid during emergency
drive operation in the fixed frequency mode or in the PID control mode.
Protective
function
Operation during
emergency drive
Protective
function
Operation during
emergency drive
Protective
function
Operation during
emergency drive
E.OC1
Retry
E.OHT
Retry
E.IOH
Output shutoff
E.OC2
Retry
E.PTC
Retry
E.SER
Disabled
E.OC3
Retry
E.OPT
Disabled
E.AIE
Disabled
E.OV1
Retry
E.OP1
Disabled
E.USB
Disabled
E.OV2
Retry
E.OP2
Disabled
E.SAF
Retry
E.OV3
Retry
E.OP3
Disabled
E.PBT
Retry
E.THT
Retry
E.16
Disabled
E.OS
Disabled
E.THM
Retry
E.17
Disabled
E.LCI
Disabled
E.FIN
Retry
E.18
Disabled
E.PCH
Disabled
E.IPF
Disabled
E.19
Disabled
E.PID
Disabled
E.UVT
Disabled
E.20
Disabled
E.1
Retry
E.ILF
Disabled
E.PE
Output shutoff
E.2
Retry
E.OLT
Retry
E.PUE
Disabled
E.3
Retry
E.SOT
Retry
E.RET
Output shutoff
E.5
Retry
E.LUP
Disabled
E.PE2
Output shutoff
E.6
Retry
E.LDN
Disabled
E.CPU
Retry
E.7
Retry
E.BE
Retry
E.CTE
Disabled
E.13
Retry
E.GF
Retry
E.P24
Disabled
E.LF
Disabled
E.CDO
Retry
Tab. 5-75:
Operation of protective functions during emergency drive
Signal
Pr. 190 to Pr. 196 setting
Description
Positive logic
Negative logic
ALM
99
199
Turns ON at the occurrence of a fault that causes the above-mentioned
"retry" or "output shutoff" during emergency drive operation.
ALM3
66
166
Output when a fault occurs during emergency drive operation.
During emergency drive operation, if a fault that does not activate any
protective function occurs, the signal turns ON for 3 s and then turns
OFF.
Tab. 5-76:
Fault output during emergency drive operation
Input signal status
Fixed frequency mode
PID control mode
Valid
OH, TRG, TRC, X51, RES, X70, X71
OH, TRG, TRC, X51, RES, X70, X71
Held
RT, X18, SQ, X84
RT, X18, SQ, X64, X65, X66, X67, X79, X84
Always-ON
—
X14, X77, X78, X80
Tab. 5-77:
Input signal operation during emergency drive operation
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......