![Mitsubishi Electric FR-F820-00046 Скачать руководство пользователя страница 323](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886323.webp)
Parameters
(H) Protective function parameter
FR-F800
5 - 151
Electronic thermal O/L relay operation characteristic for induction motor (Pr. 9)
●
This function detects the overload (overheat) of the motor and trips the inverter by stopping the
operation of the transistor at the inverter output side.
●
Set the rated current (A) of the motor in Pr. 9. (If the motor has both 50 Hz and 60 Hz ratings and
the Pr. 3 "Base frequency" is set to 60 Hz, set to 1.1 times the 60 Hz rated motor current.)
●
Set "0" in Pr. 9 to avoid activating the electronic thermal O/L relay function; for example, when
using an external thermal relay for the motor. (Note that the output transistor protection of the
inverter is activated. (E.THT))
●
When using the Mitsubishi constant-torque motor, set Pr. 71 "Applied motor" = "1, 13 to 16, 50,
53, 54". (This will set a 100% continuous torque characteristic in the low-speed range.)
When setting Pr. 9 to a value (current value) of 50% of the inverter rated current
The % value denotes the percentage to the inverter rated current. It is not the percentage to the
rated motor current.
When the electronic thermal O/L relay of the Mitsubishi constant-torque motor is set, the charac-
teristic curve is as shown in this diagram at 6 Hz or higher. (For selection of the operation
characteristic, refer to page 5-297.)
Transistor protection is activated depending on the temperature of the heatsink. The protection
may be activated even with less than 120% depending on the operating conditions.
I003018E
Fig. 5-45:
Electronic thermal relay function operation characteristic
230
52.5
%
105
%
50
100 120
150
60
120
180
240
50
60
70
Pr. 9 = 50 % setting of
inverter rating
(mi
n
) unit displa
y
in
this r
e
g
io
n
Pr. 9 = 100 % setting of
inverter rating
(s) u
n
it di
spl
a
y in this region
Opera
ti
on time (s)
O
peratio
n
time
(min)
30 Hz
or more
20 Hz
10 Hz
6 Hz
0.5 Hz
30 Hz or more
20 Hz
10 Hz
6 Hz
0.5 Hz
Operation region
Region on the right of
characteristic curve
Non-operation region
Region on the left of
characteristic curve
Characteristic when electronic thermal relay
function for motor protection is turned off
(When Pr. 9 setting is 0 (A))
Range for the
transistor
protection
Inverter output power (%)
(% to the inverter rated current)
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......