![Mitsubishi Electric FR-F820-00046 Скачать руководство пользователя страница 374](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886374.webp)
(M) Monitor display and monitor output signal
Parameters
5 - 202
When using the monitor item as the main monitor data on the LCD operation panel (FR-LU08) or
the parameter unit (FR-PU07), use Pr.774 to Pr.776 or the monitor function of the FR-LU08 or the
FR-PU07 for setting.
The cumulative energization time and actual operation time are accumulated from 0 to 65535
hours, then cleared, and accumulated again from 0.
The actual operation time does not increase if the cumulative running time before power OFF is
less than an hour.
When using the parameter unit (FR-PU07), "kW" is displayed.
!
Differs according to capacities. (FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower /
FR-F820-03160(75K) or higher, FR-F840-01800(75K) or higher)
BACnet recep-
tion status
1
81
H51
40281
Displays the BACnet reception
status.
BACnet token
pass counter
1
82
H52
40282
Displays the count of received
token.
BACnet valid
APDU counter
1
83
H53
40283
Displays the count of valid APDU
detection.
BACnet commu-
nication error
counter
1
84
H54
40284
Displays the count of
communication error detection.
BACnet terminal
FM/CA output
level
0.1%
85
H55
40285
Displays the value set in the
Analog Output object
(ID = 0: Terminal FM/CA) for
BACnet communication.
BACnet terminal
AM output level
0.1%
86
H56
40286
Displays the value set in the
Analog Output object
(ID = 1: Terminal AM) for BACnet
communication. (A display
without signs displays negative
values as absolute values.)
Remote output
value 1
0.1%
87
H57
40287
Displays the setting values of
Pr. 656 to Pr. 659 (analog remote
output).
(Refer to page 5-249.)
Remote output
value 2
0.1%
88
H58
40288
Remote output
value 3
0.1%
89
H59
40289
Remote output
value 4
0.1%
90
H5A
40290
PID manipulated
variable
0.1%
91
H5B
40291
Displays the PID control
manipulated amount.
(Refer to page 5-368)
Second PID set
point
0.1%
92
H5C
40292
Displays the set point, measured
value, and deviation under
second PID control.
(Refer to page 5-368)
Second PID
measured value
0.1%
93
H5D
40293
Second PID
deviation
0.1%
94
H5E
40294
Second PID
measured value
2
0.1%
95
H5F
40295
Displays PID measured value
even if PID control operating
conditions are not satisfied while
the PID control is enabled (Pr.753
≠
"0").
(Refer to page 5-368)
Second PID
manipulated
variable
0.1%
96
H60
40296
Displays the second PID control
manipulated amount.
(Refer to page 5-368)
Control circuit
temperature
1 °C
98
H62
40298
Displays the temperature of the
control circuit board.
Without minus sign: 0 to 100 °C
With minus sign: –20 to 100 °C
Types of
monitor
Unit
Pr. 52,
Pr. 774 to Pr. 776,
Pr. 992
RS-485
communica-
tion dedicat-
ed monitor
(hexadeci-
mal)
MODBUS®
RTU real
time
monitor
Minus (-)
display
Description
Tab. 5-87:
Monitor description list (4)
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......