Parameters
(H) Protective function parameter
FR-F800
5 - 189
5.7.12
Load characteristics fault detection
This function is used to monitor whether the load is operating in normal condition by storing the
speed/torque relationship in the inverter to detect mechanical faults or for maintenance. When the
load operating condition deviates from the normal range, the protective function is activated or the
warning is output to protect the inverter or the motor.
Pr.
Name
Initial value
Setting range Description
FM
CA
1480
H520
Load characteristics
measurement mode
0
0
Load characteristics measurement is normally
completed.
1
Load characteristics measurement mode is
started.
2, 3, 4, 5, 81, 82,
83, 84, 85
The load characteristics measurement status is
displayed. (Read-only)
1481
H521
Load characteristics
load reference 1
9999
0 to 400%
Set the reference value of normal load
characteristics.
8888: The present load status is written as
reference status.
9999: The load reference is invalid.
1482
H522
Load characteristics
load reference 2
9999
1483
H523
Load characteristics
load reference 3
9999
1484
H524
Load characteristics
load reference 4
9999
1485
H525
Load characteristics
load reference 5
9999
1486
H526
Load characteristics
maximum frequency
60 Hz
50 Hz
0 to 590 Hz
Set the maximum frequency of the load
characteristics fault detection range.
1487
H527
Load characteristics
minimum frequency
6 Hz
0 to 590 Hz
Set the minimum frequency of the load
characteristics fault detection range.
1488
H531
Upper limit warning
detection width
20%
0 to 400%
Set the detection width when the upper limit
load fault warning is output.
9999
Function disabled
1489
H532
Lower limit warning
detection width
20%
0 to 400%
Set the detection width when the lower limit load
fault warning is output.
9999
Function disabled
1490
H533
Upper limit fault
detection width
9999
0 to 400%
Set the detection width when output is shut off
when the upper limit load fault occurs.
9999
Function disabled
1491
H534
Lower limit fault
detection width
9999
0 to 400%
Set the detection width when output is shut off
when the lower limit load fault occurs.
9999
Function disabled
1492
H535
Load status detection
signal delay time / load
reference
measurement waiting
time
1 s
0 to 60 s
Set the waiting time after the load fault is
detected until warning output or output shutoff.
In the load characteristics measurement mode,
set the waiting time after the load measurement
frequency is reached until the load reference is
set.
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......