![Mitsubishi Electric FR-F820-00046 Скачать руководство пользователя страница 121](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886121.webp)
Precautions for use of the inverter
Electro-magnetic interference (EMI) and leakage currents
FR-F800
3 - 7
I001049E
Fig. 3-4:
Noise paths
Noise
propagation
path
Countermeasure
When devices that handle low-level signals and are liable to malfunction due to electromagnetic
noises, e.g. instruments, receivers and sensors, are contained in the enclosure that contains the inverter
or when their signal cables are run near the inverter, the devices may malfunction due to by air-
propagated electromagnetic noises. The following countermeasures must be taken:
Install easily affected devices as far away as possible from the inverter.
Run easily affected signal cables as far away as possible from the inverter and its I/O cables.
Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do
not bundle them.
Set the EMC filter ON/OFF connector of the inverter to the ON position. (Refer to page 3-9.)
Inserting a line noise filter into the output suppresses the radiated noise from the cables.
Use shielded cables as signal cables and power cables and run them in individual metal conduits to
produce further effects.
When the signal cables are run in parallel with or bundled with the power cables, magnetic and static
induction noises may be propagated to the signal cables to cause malfunction of the devices and the
following countermeasures must be taken:
Install easily affected devices as far away as possible from the inverter.
Run easily affected signal cables as far away as possible from the inverter and its I/O cables.
Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do
not bundle them.
Use shielded cables as signal cables and power cables and run them in individual metal conduits to
produce further effects.
When the power supplies of the peripheral devices are connected to the power supply of the inverter
in the same line, inverter-generated noises may flow back through the power supply cables to cause
malfunction of the devices and the following countermeasures must be taken:
Set the EMC filter ON/OFF connector of the inverter to the ON position. (Refer to page 3-9.)
Install the line noise filter (FR-BLF, FR-BSF01) to the power cables (output cables) of the inverter.
When a closed loop circuit is formed by connecting the peripheral device wiring to the inverter, leakage
currents may flow through the earthing (grounding) cable of the inverter to cause the device to
malfunction. In that case, disconnecting the earthing (grounding) cable from the device may stop the
malfunction of the device.
Tab. 3-4:
Noise and Countermeasures
+
,
)
*
)
Instrument
Receiver
Inverter
Telephone
Sensor power
supply
Sensor
M
3~
Motor
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......