Parameters
(T) Multi-Function Input Terminal Parameters
FR-F800
5 - 275
Calibration of analog input bias and gain
(C16 (Pr. 919) to C19 (Pr. 920), C38 (Pr. 932) to C41 (Pr. 933))
●
"Bias"/"gain" function can adjust the relation between the stall prevention operation level and the
setting input signal.
Examples of setting input signals are 0 to 5 V DC, 0 to 10 V DC, or 4 to 2 mA DC, and they are
externally input.
●
Set the bias value of the terminal 1 input using C16 (Pr. 919).
(Shipped from factory with the stall prevention operation level for 0 V)
●
Set the stall prevention operation level against the input voltage set by Pr. 73 "Analog input
selection" with C18 (Pr. 920). (Initial value is 10 V.)
●
Set the bias value of the terminal 4 input using C38 (Pr. 932).
(The initial value is the stall prevention operation level for 4 mA.)
●
Set the the stall prevention operation level against the 20 mA for input current (4 to 20 mA) with
C40 (Pr. 933).
I002648E
Fig. 5-125:
Signal adjustment of terminal 1
I002649E
Fig. 5-126:
Signal adjustment of terminal 4
400
150
0
0
0
Gain
C18 (Pr. 920)
Analog input
100%
5 V
10 V
C19 (Pr. 920)
C17 (Pr. 919)
–150
Calibration example of terminal 1
Bias
C16 (Pr. 919)
Stall prevention operation level (%)
(-5 V)
(-10 V)
-100 %
Initial value
*
* If a negative command is given, the stall prevention operation level is regarded as "0".
400
150
Bias
C38
(Pr. 932)
Gain
C40
(Pr. 933)
100 %
20 mA
C41 (Pr. 933)
Analog input
0
20
0
4
C39 (Pr. 932)
Initial value
Calibration example of terminal 4
Stall prevention operation level (%)
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......