(A) Application parameters
Parameters
5 - 344
●
When Pr. 248 = "1", the MC1 signal is turned OFF when the protective function is activated due to
any cause.
●
When Pr. 248 = "2", the MC1 signal is turned OFF only when the protective function is activated
due to an error resulted from a failure in the inverter circuit or a wiring error (refer to the following
table). (For the alarm details, refer to page 6-9.)
●
To enable the self power management function for the separated converter type, enable the self
power management function also on the converter unit side. To activate the self power manage-
ment function when a converter unit fault occurs, connect the terminal to which Y17 signal of the
converter unit is assigned and the terminal to which X94 signal of the inverter is assigned.
Fault record
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (E.PE)
Parameter storage device fault (E.PE2)
24 VDC power fault (E.P24)
Operation panel power supply short circuit
RS-485 terminals power supply short circuit (E.CTE)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Brake transistor alarm detection (E.BE)
Internal circuit fault (E.13/E.PBT)
Tab. 5-162:
Fault record at Pr. 248 = "2"
Y17 output signal
(on the converter unit side)
MC1 output signal
(inverter side)
MC1 output signal actual
operation
Main circuit power supply
OFF
OFF
OFF
Stop
OFF
ON
OFF
Stop
ON
OFF
OFF
Stop
ON
ON
ON
Supplied
Tab. 5-163:
Signals Y17 and MC1 for self power management function with separated converter type
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......