Parameters
(G) Control parameters
FR-F800
5 - 553
Details of the setting value
●
FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower
●
FR-F820-03160(75K) or higher, FR-F840-01800(75K) or higher
●
FR-F842-07700(355K) or higher
While the power is supplied only to the control circuit with Pr. 30 = "100 or higher", the inverter
reset is not performed when the power is supplied to the main circuit.
When using brake unit (FR-BU2, BU, FR-BU)
(FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower)
When using FR-BU2 in combination with GZG/GRZG/FR-BR, or using BU or FR-BU, set Pr. 30 = "0 (initial
value), 10, 20, 100, 110, 120".
When using brake unit (FR-BU2)
(FR-F820-03160(75K) or higher, FR-F840-01800(75K) or higher)
To use FR-BU2 in combination with MT-BR5, set as follows.
●
Set Pr. 30 = "1, 11, 21".
●
Set the brake unit FR-BU2, Pr. 0 "Brake mode selection" = "2".
When using power regeneration converter (MT-RC)
●
Set Pr. 30 = "1, 11, 21".
Regeneration unit
Power supply terminals of inverter
Pr. 30 Setting
Brake unit (FR-BU2 (GZG/GRZG/
FR-BR), FR-BU, BU)
R, S, T
0 (initial value), 100
P, N
10, 110
R, S, T/P, N
20, 120
High power factor converter
(FR-HC2),
Power regeneration common converter
(FR-CV)
P, N
2, 102
For manufacturer setting. Do not set.
1, 11, 21, 101, 111, 121
Tab. 5-282:
FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower
Regeneration unit
Power supply terminals of inverter
Pr. 30 Setting
Without regenerative function
R, S, T
0 (initial value), 100
P, N
10, 110
R, S, T/P, N
20, 120
Brake unit (FR-BU2 (MT-BR5))
R, S, T
1, 101
P, N
11, 111
R, S, T/P, N
21, 121
Power regeneration converter (MT-RC)
R, S, T
1, 101
High power factor converter (FR-HC2)
P, N
2, 102
Tab. 5-283:
FR-F820-03160(75K) or higher, FR-F840-01800(75K) or higher
Regeneration unit
Pr. 30 Setting
Without regenerative function (FR-CC2)
10 (initial value), 110
Brake unit (FR-CC2 + FR-BU2 (MT-BR5))
11, 111
High power factor converter (FR-HC2)
2, 102
Tab. 5-284:
FR-F842-07700(355K) or higher
NOTE
When Pr. 30 = "1, 11, 21", oL (stall prevention (overvoltage)) does not operate.
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......