(H) Protective function parameter
Parameters
5 - 186
Stall prevention operation level setting (analog variable) from terminal 1 (terminal 4)
(Pr. 148, Pr. 149, Pr. 858, Pr. 868)
●
To use the terminal 1 (analog voltage input) to set the stall prevention operation level, set Pr. 868
"Terminal 1 function assignment" = "4". Then, input a 0 to 5 V (or 0 to 10 V) to the terminal 1. To
choose whether 5 V or 10 V, use Pr. 73 "Analog input selection". In the initial status, Pr. 73 = "1 (initial
value)" is set to choose 0 to ±10 V input.
●
When setting the stall prevention operation level from terminal 4 (analog current input), set Pr. 858
"Terminal 4 function assignment" = "4".
●
Input 0 to 20 mA into terminal 4. There is no need to turn ON the AU signal.
●
Set Pr. 148 "Stall prevention level at 0 V input" to the current limit level when input voltage is 0 V
(0 mA).
●
Set Pr. 149 "Stall prevention level at 10 V input" to the current limit level when input voltage is
10 V/5 V (20 mA).
When Pr. 868 = "4" (analog stall prevention), the other functions for terminal 1 (auxiliary input,
override function, PID control) will be disabled.
When Pr. 858 = "4" (analog stall prevention), PID control and speed commands using terminal 4
will not operate, even if the AU signal turns ON.
When both of Pr. 858 and Pr. 868 are set to "4" (stall prevention), terminal 1 functions take priority
and terminal 4 has no function.
I002600E
Fig. 5-69:
Stall prevention operation level setting by terminal 1
Pr. 858 setting
Pr. 868 setting
V/F, Advanced magnetic flux vector control
Terminal 4 function
Terminal 1 function
0
(initial value)
0
(initial value)
Frequency command
(AU signal-ON)
Auxiliary frequency
Stall prevention
9999
⎯
0
(initial value)
Stall prevention
Auxiliary frequency
⎯
Stall prevention
9999
Stall prevention
⎯
9999
⎯
⎯
⎯
Tab. 5-82:
Functions of terminal 1 and 4 in dependence of the control mode
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
100%
50%
200%
150%
Set the current limit level at 10 V/5 V input
power (input current 20 mA) using Pr. 149.
Input voltage (V)
Input current (mA)
(5 V/10 V DC)
(20 mA)
Set the current limit level at 0 V input
voltage (input current 0 mA) using Pr. 148.
Current limit level (%)
Initial value
(–5 V/10 V DC)
0 V
0 mA
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......