Basic operation procedure (External operation)
Basic operation
4 - 28
4.6.5
Using an analog signal (current input) to give a frequency command
Connection diagram
NOTES
Turn ON the STF (STR) signal to give a start command.
Turn ON the AU signal.
Set Pr. 79 "Operation mode selection" = "2" (External operation mode).
I002447E_G
Fig. 4-11:
Frequency setting by analog current input
Example
Operation example: Operate at 60 Hz.
Operation
Screen at power-ON
The monitor display appears.
Terminal 4 input selection
Turn ON the terminal 4 input selection signal (AU). Input to the terminal 4 is enabled.
Start
Turn ON the start switch (STF or STR). [FWD] or [REV] flickers as no frequency command is given.
Acceleration
➔
constant speed
Input 20 mA. The frequency value on the indication increases in Pr. 7 "Acceleration time", and "
" (60.00 Hz)
appears. [FWD] indicator is lit during the forward rotation, and [REV] indicator is lit during the reverse rotation.
!
Deceleration
Input 4 mA or less. The frequency value on the indication decreases in Pr. 8 "Deceleration time", and the motor stops
rotating with "
" (0.00 Hz) displayed. [FWD] or [REV] indicator flickers.
Stop
Turn OFF the start switch (STF or STR). [FWD] or [REV] indicator turns OFF.
Tab. 4-19:
Operate the inverter by using the analog current input
NOTES
When both the forward rotation switch (STF) and the reverse rotation switch (STR) are ON, the
motor cannot be started. If both are turned ON while the motor is running, the motor decelerates
to a stop.
Pr. 184 "AU terminal function selection" must be set to "4" (AU signal) (initial value).
Parameters referred to
Pr. 7, Pr. 8
Acceleration time, Deceleration time
=>
Pr. 184
AU terminal function selection
=>
5(-)
4(+)
STF
STR
PC
AU
Inverter
Current signal
source
(4–20 mA DC)
Reverse rotation start
Switch
Forward rotation start
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......