Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 245
●
Select whether the inverter output stops or the inverter operation continues when Y12 signal
turns ON, by setting Pr.167.
Zero current detection (Y13 signal, Pr. 152, Pr. 153)
●
If the output during inverter running remains lower than the Pr. 152 setting for the time set in
Pr. 153 or longer, the Zero current detection (Y13) signal is output from the inverter's open
collector or relay output terminal.
●
Once turned ON, the zero current detection time signal (Y13) is held ON for at least 0.1s.
●
If the inverter output current drops to "0", because torque is not generated, slippage due to gravity
may occur, especially in a lift application.
To prevent this, the Y13 signal, which closes the mechanical brake at "0" output current, can be
output from the inverter.
●
For the Y13 signal, set "13 (positive logic) or 113 (negative logic)" in any of Pr. 190 to Pr. 196 (output
terminal function selection) to assign the function to the output terminal.
●
Select whether the inverter output stops or the inverter operation continues when Y13 signal
turns ON, by setting Pr.167.
Pr. 167 setting
When Y12 signal turns ON
When Y13 signal turns ON
0 (Initial value)
Continuous operation
Continuous operation
1
Inverter trip (E.CDO)
Continuous operation
10
Continuous operation
Inverter trip (E.CDO)
11
Inverter trip (E.CDO)
Inverter trip (E.CDO)
Tab. 5-106:
Selecting the behaviour of the inverter output at switching of Y12 and Y13
I001156E
Fig. 5-102:
Zero current detection
NOTES
The signals are enabled even when online or offline auto tuning is being executed.
The response time of the Y12 and Y13 signals is approximately 0.1 s. Note that the response time
varies with the load.
When Pr. 152 = "0", detection is disabled.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Pr. 167 = "0"
Output current
Pr. 152
0 [A]
Zero current
detection signal
(Y13)
Pr. 152
Pr. 153
Detection time
Time
Start signal
0.1 s *
ON
Pr. 153
Detection time
OFF
ON
OFF
ON
OFF
* When the output is restored to the Pr. 152 level, the Y13signal is turned OFF after 0.1 s.
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......