CANopen communication
5.3
Transmitting process data
95
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
[5-8]
Mapping contents
Comparison value:
Here you can specify a value which, by comparison with the current counter
content, is able to influence the counter output or trigger a process alarm. The response of the
output or of the process alarm can be parameterised.
Set value:
With an edge change 0-1 of
COUNTERVAL_SET
in the control word, the set value is
accepted in the counter.
Count value:
Current counter content
Latch value:
If there is a positive edge at the latch input, the count value is stored here.
Ticker value:
After mains connection, a timer (
s ticker) is started which restarts at 0 after 65535
s.
With every change of the count value, the time value of the timer is stored as 16-bit-
s value
together with the count value in the input area.
Counter modules EPM-S600 ... EPM-S603 – control and status words
Default mapping
Word
EPM-S600
EPM-S601
EPM-S602
EPM-S603
EPM-S604
1
Comparison
value
Comparison
value C1
Comparison
value
Control word C1
-
2
Control word C2
3
Set value
Comparison
value C2
Set value
-
4
5
Control word
Control word C1
Control word
6
-
Control word C2
-
7
-
8
9
Counter value
Count value C1
Counter value
Count value C1
Encoder value
10
11
Latch value
Count value C2
Status word
Count value C2
Ticker value
12
Ticker value
13
Status word
Status word C1
-
Status word C1
-
14
Ticker value
Status word C2
Status word C2
15
-
-
-
16
PDOx-Rx
PDOx-Rx
PDOx-Tx
PDOx-Tx
EPM-S1
10
EPM-S6xx
1
5
9
13
2
6
10
14
3
7
11
15
4
8
12
16
402
h
508
h
382
h
482
h
Node-ID = 2