5
CANopen communication
5.8
Parameterising analog I/Os
117
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.8.6
2 analog inputs 0/4 ... 20 mA (16 bits) - EPM-S408
Parameter data
Index/subindex
Name
Description/value
Lenze
I-3100/x
Diagnostics
Bit 0 ... 5: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
0x00
I-3101/x
Reserved
0
I-3102/x
Limit value
monitoring
Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: reserved
0x00
I-3103/x
Interference
frequency
suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 7 ... 4: Reserved
0x00
I-3104/x
Function channel 1
48 (0x30): 4 ... 20 mA / -4864 ... 32511
64 (0x40): 4 ... 20 mA / -3277 ... 20480
49 (0x31): 0 ... 20 mA / -4864 ... 32511
65 (0x41): 0 ... 20 mA / -3277 ... 20480
255 (0xFF): Channel deactivated
0x41
I-3105/x
Reserved
0
I-3106/x
I-3107/x
Upper limit value
channel 1
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
I-3108/x
I-3109/x
Lower limit value
channel 1
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is active, a
process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000
I-310A/x
Function channel 2
48 (0x30): 4 ... 20 mA / -4864 ... 32511
64 (0x40): 4 ... 20 mA / -3277 ... 20480
49 (0x31): 0 ... 20 mA / -4864 ... 32511
65 (0x41): 0 ... 20 mA / -3277 ... 20480
255 (0xFF): Channel deactivated
0x41
I-310B/x
Reserved
0
I-310C/x
I-310D/x
Upper limit value
channel 2
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
I-310E/x
I-310F/x
Lower limit value
channel 2
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is active, a
process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000