
5
CANopen communication
5.3
Transmitting process data
91
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Ticker values EPM-S207 and EPM-S310
Bit
Name
Function
0 ... 15
Ticker value
After mains connection, a timer (
s ticker) is started, which after 65535
s
starts with 0 again.
Running number, channel status EPM-S207
Bit
Name
Function
0 ... 7
Running number (RN)
Counter counting from 0 ... 63 and recommencing at 0.
In the first run, the "running number" must start with 1.
8
Channel status DI1
0: FALSE
1: TRUE
9
Channel status DI2
0: FALSE
1: TRUE
10 ... 15
–
Reserved (fix 0)
Running number, channel status EPM-S310
Bit
Name
Function
0 ... 7
Running number (RN)
Counter counting from 0 ... 63 and recommencing at 0.
In the first run, the "running number" must start with 1.
8 ... 11
–
Reserved (fix 0)
12
Enable DO1
0: Inhibit
1: Enable
13
Enable DO2
14
Channel status DO1
0: FALSE
1: TRUE
15
Channel status DO2
0: FALSE
1: TRUE