5
CANopen communication
5.8
Parameterising analog I/Os
119
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.8.7
2 analog outputs 0 ... 10 V (12 bits) - EPM-S500
Parameter data
With the formulas listed in the following you can convert a digital value into an analog output value
and vice versa.
Index/subindex
Name
Description/value
Lenze
I-3100/x
Reserved
0
I-3101/x
Short-circuit
detection
Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2
Bit 2 ... 7: Reserved
0x00
I-3102/x
Function channel 1
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
I-3103/x
Function channel 2
0x20
I-3104/x
Reserved
...
...
...
I-311D/x
Reserved
0
Measuring range
Voltage (U)
dec
hex
Range
Conversion
(Fct. no.)
[V]
0 ... 10 V
(0x10)
11.76
32511
7EFF
Overflow
U = D * 10 / 27648
D = 27648 * U / 10
10
27648
6C00
Nominal range
5
13824
3600
0
0
0000
Not possible, is limited to 0 V
Underflow
0 ... 10 V
(0x20)
12.5
20480
5000
Overflow
U = D * 10 / 16384
D = 16384 * U / 10
10
16384
4000
Nominal range
5
8192
2000
0
0
0000
Not possible, is limited to 0 V
Underflow