Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
424
8
DeviceNet communication
8.4
Parameterising temperature measurement
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8
Conversion time
channel 1
You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for each
channel.
0 (0x00): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz: 270.5
ms/channel 16 bits
1 (0x01): at 50 Hz: 164.2 ms/channel 16 bits;
at 60 Hz: 137.2 ms/channel 16 bits
2 (0x02): At 50 Hz: 84.2 ms/channel 16 bits;
at 60 Hz: 70.5 ms/channel 16 bits
3 (0x03): At 50 Hz: 44.1 ms/channel 16 bits;
at 60 Hz: 37.2 ms/channel 16 bits
4 (0x04): At 50 Hz: 24.2 ms/channel 16 bits;
at 60 Hz: 20.5 ms/channel 16 bits
5 (0x05): At 50 Hz: 14.2 ms/channel 16 bits;
at 60 Hz: 12.2 ms/channel 16 bits
6 (0x06): At 50 Hz: 9.2 ms/channel 16 bits;
at 60 Hz: 8.0 ms/channel 16 bits
7 (0x07): At 50 Hz: 6.6 ms/channel 15 bits;
at 60 Hz: 5.9 ms/channel 15 bits
8 (0x08): At 50 Hz: 4.2 ms/channel 13 bits;
at 60 Hz: 3.8 ms/channel 13 bits
0x00
9
Upper limit value
channel 1
You can define an upper or lower limit value for each
channel. For this you can only specify values from the
nominal range, otherwise you'll receive a parameterisation
error. By specification of 0x7FFF for the upper or 0x8000 for
the lower limit value, the corresponding limit value is
deactivated.
If your measured value is outside a limit value and you have
activated the limit value monitoring, a process alarm is
triggered.
0x7FFF
10
Lower limit value
channel 1
0x8000
Channel 2
11
Function channel 2
See channel 1
0x50
12
Conversion time
channel 2
See channel 1
0x00
13
Upper limit value
channel 2
See channel 1
0x7FFF
14
Lower limit value
channel 2
0x8000
Channel 3 (for two-wire conductor connections only)
15
Function channel 3
See channel 1
0x50
16
Conversion time
channel 3
See channel 1
0x00
17
Upper limit value
channel 3
See channel 1
0x7FFF
18
Lower limit value
channel 3
0x8000
Channel 4 (for two-wire conductor connections only)
19
Function channel 4
See channel 1
0x50
20
Conversion time
channel 4
See channel 1
0x00
Position in
string
Name
Description/value
Lenze
No.