6
PROFIBUS communication
6.10
Parameterising technology modules
311
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Option 14, cable assignment
0x80 15
Cable assignment
For a connection with minimum reflections and the open
circuit detection in RS422/485 operation, the cables can be
pre-assigned via parameters with a defined idle level.
• 0x00:
No pre-assignment of the receive path. This setting is only
advisable for special drivers that are provided with a bus
capability.
• 0x01:
Signal R(A) 5V (open-circuit monitoring), signal R(B) 0V
In full duplex operation under RS422, open-circuit
monitoring is possible.
• 0x02:
Signal R(A) 0V, signal R(B) 5V
This pre-assignment corresponds to the idle state (no
transmitter active) in half duplex operation under RS485.
Open-circuit monitoring is not possible.
0x00
Data set
Name
Description/value
Lenze
No.
Byte