Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
172
5
CANopen communication
5.14
"Save" function
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.14
"Save" function
All parameter changes and the structure of the station are permanently stored via index I-1010
(Store parameter).
Note!
If the real structure of the station does not correspond with its stored structure anymore
after a restart, the bus coupler module reports an error.
• The LED SF (red) is lit permanently.
• The LED PWR (green) is lit permanently.
• The LED CAN-RUN (green) is blinking.
The stored structure of the station is deleted via index I-1011 (Restore all parameters).
Index
Name
Possible settings
Info
Lenze
Selection
I-1010
Save All Parameters
0
Saving the parameter settings and
the station structure in the
EEPPROM of the bus coupler.
Function in accordance with
CANopen (DS301/DS401
communication protocol).
0
Number of subindexes assigned
Display of the subindices user by
the index I-1010
1 Save
0 = no function
1702257011 = save parameters
The numerical value is ASCII-coded
and complies with:
65 76 61 0x73 = "E" "V" "A" "S"