Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
536
9
PROFINET communication
9.8
Parameterising the counter
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.8.4
2 counters 32 bits, 24 V DC - EPM-S603
By integration of the GSE file VI010C19.gse you can specify all counter parameters via a hardware
configuration.
The following functions can be parameterised:
Read data: 12 bytes
Write data: 4 bytes
Counter modules EPM-S600 ... EPM-S603 – control and status words
Counting functions
Description
Continuous counting
The counter counts from 0 to the counting limit, then skips to the opposite counting
limit and continues to count from there.
Signal evaluation
Description
Single rotary transducer
Connection to "A/pulse" input
Double rotary transducer
Quadruple rotary transducer Connection to input "A/pulse" and "B/direction"
Direction
Pulse at "A/pulse" input and direction at "B/direction" input
Additional functions
Description
Gate function
The gate function serves to start, stop, and interrupt a counting function. In the case
of this counter the internal gate (I-gate) is conform to the software gate (SW gate)
which you control via your user program (status word in the output area).
Input area in the process image
Addr.
Access
Assignment
+0
Double word
Counter 1: count value
+4
Double word
Counter 2: count value
+8
Word
Counter 1: Status word
+10
Word
Counter 2: Status word
Output area in the process image
Addr.
Access
Assignment
+0
Word
Counter 1: Control word
+2
Word
Counter 2: Control word