
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
334
7
EtherCAT communication
7.5
Parameterising analog I/Os
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.5.5
2 analog inputs -10 ... +10 V (16 bits) - EPM-S406
Parameter data
Subindex Name
Description/value
Lenze
01
Diagnostics
Bit 0 ... 5: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
0x00
02
Reserved
0
03
Limit value
monitoring
Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: reserved
0x00
04
Interference
frequency
suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 7 ... 4: Reserved
0x00
05
Function channel 1
12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
06
Reserved
0
07
Upper limit value
channel 1
Value from the rated range; if this value is exceeded and the limit
value monitoring function is active, a process alarm is triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
08
Lower limit value
channel 1
Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is active, a process
alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000
09
Function channel 2
12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
0A
Reserved
0
0B
Upper limit value
channel 2
Value from the rated range; if this value is exceeded and the limit
value monitoring function is active, a process alarm is triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
0C
Lower limit value
channel 2
Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is active, a process
alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000