PROFINET communication
9.9
Parameterising the encoder evaluation
539
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.9
Parameterising the encoder evaluation
9.9.1
SSI - EPM-S604
By integration of the GSE file VI010C19.gse you can specify all counter parameters via a hardware
configuration.
The following functions can be parameterised:
Read data: 6 bytes
Encoder value:
current encoder value
Ticker value:
After mains connection, a timer (
s ticker) is started which restarts at 0 after 65535
s.
With every change of the encoder value, the time value of the timer is stored as 16-bit-
s value
together with the count value in the input area.
Functions
Description
SSI encoder parameters
According to encoder data sheet
Operating mode
Master mode or monitoring operation
Alarm response
With definition of the comparison and limit values
Input area
Addr.
Access
Assignment
+0
Double word
Encoder value
+4
Word
Ticker value