Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
62
4
Configuring the I/O system in the »PLC Designer«
4.3
Mapping the real station structure in the »PLC Designer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CAN baud rate setting
14. Double-click the "CANbus" device in the
device view
to open its settings.
15. Set the baud rate in the
CANbus
tab:
Note!
• The baud rate set in the »PLC Designer« overwrites the baud rate set for the field devices
via »WebConfig«/»EASY Starter«/»Engineer«/»Global Drive Control«.
• In a CANopen network, set the same baud rate for all nodes.
Setting sync generation
Sync generation is required if ...
• at least one PDO with sync-controlled processing is used on the bus;
• the applications are to run in synchronism in several field devices;
• Motion devices are to be operated on the fieldbus.
In order to activate the Sync generation:
16. Double-click the "CANopen_Manager_MC_CAN2" device in the
device view
to open its
settings.
17. Go to the
CANopen_Manager
tab:
•
Activate the
Sync generation
option.
•
Set the sync cycle time in the
Cycle Period
entry field.