Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
182
5
CANopen communication
5.19
Diagnostics
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.19.1.1
Error codes
Error
code
Meaning
Error information
1
2
3
4
5
0x0000
Reset Emergency
0x00
0x00
0x00
0x00
0x00
0x8100
Heartbeat consumer
Node ID
LOW byte
timer value
HIGH byte
timer value
0x00
0x00
0x8130
Node guarding error
LOW byte
guard time
HIGH byte
guard time
LifeTime
0x00
0x00
0x8157
Module removed from
slot [n]; no
communication
0x05
0x[n]
0x00
0x00
0x00
0x8210
PDO not executed due to
length error
PDO number Wrong length PDO length
0x00
0x00
0x8220
PDO length exceeded
PDO number
0x1000
PDO number
0x00
0x00
0x1000
Module configuration
was changed
0x01
0x00
0x00
0x00
0x00
0x1000
Error during initialisation
of the backplane
modules
0x02
Module
number
LOW byte
Error register
HIGH byte
Error register
0x00
0x1000
Diagnosealarm
0x40 +
module
number
Diagnostic
byte 1
Diagnostic
byte 2
Diagnostic
byte 3
Diagnostic
byte 4
0x0000
Process alarm
0x80 +
module
number
Diagnostic
byte 1
Diagnostic
byte 2
Diagnostic
byte 3
Diagnostic
byte 4
0x1000
Backplane bus:
Initialisation error
E0
Module
number
LOW byte
Error bitfield
HIGH byte
Error bitfield
0x00
0x1000
Backplane bus:
Initialisation error Pre-
Operational
Operational
E0
0x00
0x00
0x00
0x00
0x1000
Backplane bus: Bus error
E1
0x00
0x00
0x00
0x00
0x1001
Lenze PDO control,
monitoring time
exceeded
FF
0x10
PDO number
Monitoring time that has
been set in [ms]
0x2000
Description of the
process data width not
permissible for modules
with time stamp
functionality or serial
interfaces
(I-3100/x, I-3101/x)
E2
0x00
0x00
0x00
0x00