5
CANopen communication
5.18
Monitoring
179
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.18.2
Monitoring of the digital outputs
Use index I-6206I-6206 to configure the response of the digital outputs if no telegram, node
guarding event, or heartbeat have been received within the defined monitoring time.
Individual response setting
Via index I-6207, the response can be individually configured for each digital output.
Index
Name
Possible settings
Info
Lenze
Selection
I-6206
Error mode - digital
output
0
{1}
255 Configures digital output
monitoring
I-
6206
0
All digital outputs retain
the last status output.
255
Response from I-6207
In I-6207, the response can be
configured individually for each
digital output
1 Byte 1
0
2 Byte 2
0
... ...
...
80 Byte 80
0
Index
Name
Possible settings
Info
Lenze
Selection
I-6207
Configures
the
individual
digital
output
responses
Error value - digital
output
0
0
{1}
255 Configures the individual digital
output responses
I-6207
8 bits of information
Bit
value
0
Output switches to LOW
Bit
value
1
Output retains last status
output
1 Byte 1
0
2 Byte 2
0
... ...
...
64 Byte 80
0