SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0498
User Action:
Complete the following steps:
1. Check the event log of XClarity Controller for any fan- or cooling-related issues or power-related
issues.
2. Make sure that the airflow at the front and rear of the enclosure is not obstructed and that fillers are in
place, clean and correctly installed.
3. Make sure that the room temperature is within operating specifications.
•
FQXSPCA0015J: Sensor [SensorElementName] has transitioned from normal to non-critical state.
This message is for the use case when an implementation has detected a Sensor transitioned to non-
critical from normal.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - Temperature
SNMP Trap ID: 12
CIM Prefix: PLAT CIM ID: 0520
User Action:
Complete the following steps:
1. Check the event log of System Management Module 2 (SMM2) and XClarity Controller for any fan- or
cooling-related issues or power-related issues.
2. Make sure that the airflow is not obstructed and that fillers are in place, clean and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Reseat the M.2 adapter if the problem still exists.
•
FQXSPCA0017M: Sensor [SensorElementName] has transitioned to critical from a less severe
state.
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0522
User Action:
Complete the following steps:
1. Check the event log on XClarity Controller and SMM2 Web GUI for any fan- or cooling-related issues
or power-related issues.
2. Make sure that the airflow at the front and rear of the enclosure is not obstructed and that fillers are in
place, clean and correctly installed.
3. Make sure that the room temperature is within operating specifications.
•
FQXSPCA0019N: Sensor [SensorElementName] has transitioned to non-recoverable from a less
severe state.
66
ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference
Содержание 7D1J
Страница 4: ...ii ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 8: ...4 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 174: ...170 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 238: ...234 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 242: ...238 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 244: ...240 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 245: ......
Страница 246: ......