•
0201020C: SMM2 Brd 5V: Voltage sensor, critical event was asserted, reading value %V (Threshold
%V)
Asserted when voltage sensed on 5V power rail is lower than lower critical threshold.
Severity: Error
Alert Category: System - SMM2 system event
SNMP Trap ID: 33620492
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
•
0201020D: SMM2 Brd 12V: Voltage sensor, critical event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 12V power rail is lower than lower critical threshold.
Severity: Error
Alert Category: System - SMM2 system event
SNMP Trap ID: 33620493
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
•
0201020E: SMM2 Brd VBAT: Voltage sensor, critical event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on coin battery output voltage is lower than lower critical threshold.
Severity: Error
Alert Category: System - SMM2 system event
SNMP Trap ID: 33620494
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
coin battery on the SMM2 module. (Service technician only)
4. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
5. If the event persists, please consult with technical service.
•
02010708: SMM2 Brd 1.15V: Voltage sensor, warning event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 1.15V power rail is higher than high non-critical threshold.
14
ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference
Содержание 7D1J
Страница 4: ...ii ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 8: ...4 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 174: ...170 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 238: ...234 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 242: ...238 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 244: ...240 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 245: ......
Страница 246: ......