SNMP Trap ID: 33622284
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
•
0201090D: SMM2 Brd 12V: Voltage sensor, critical event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 12V power rail is higher than upper critical threshold.
Severity: Error
Alert Category: System - SMM2 system event
SNMP Trap ID: 33622285
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
•
04010079: Fan 1 Tach A: Fan sensor, warning event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when fan tach reading is below warning threshold in RPM.
Severity: Warning
Alert Category: Thermal - System Thermal event
SNMP Trap ID: 67174521
User Action:
1. Ensure the indicated fan module properly installed.
2. If the event persists, reseat the indicated fan module. (Service technician only)
3. If the event persists, replace the indicated fan module. (Service technician only)
4. If the event persists, please consult with technical service.
•
0401007A: Fan 1 Tach B: Fan sensor, warning event was asserted, reading value %RPM (Threshold
%RPM)
Asserted when fan tach reading is below warning threshold in RPM.
Severity: Warning
Alert Category: Thermal - System Thermal event
SNMP Trap ID: 67174522
User Action:
1. Ensure the indicated fan module properly installed.
2. If the event persists, reseat the indicated fan module. (Service technician only)
3. If the event persists, replace the indicated fan module. (Service technician only)
4. If the event persists, please consult with technical service.
18
ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference
Содержание 7D1J
Страница 4: ...ii ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 8: ...4 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 174: ...170 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 238: ...234 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 242: ...238 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 244: ...240 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 245: ......
Страница 246: ......