106F0401: EvtLogDisabled: Event Logging Disabled, SEL Full was asserted.
SMM2 system event log is 100% full.
Severity: Error
Alert Category: System - SMM2 system event
SNMP Trap ID: 275710977
User Action:
Check or backup the system event log and then clear it immediately.
•
106F0501: EvtLogDisabled: Event Logging Disabled, SEL Almost Full was asserted.
SMM2 system event log is at least 75% full.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 275711233
User Action:
No action is required. Beware of the system event log is almost full.
•
18070105: Encl Conf Check: Chassis, transition to Non-Critical from OK was asserted.
The setting of power supply is not match to current configuration.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112197
User Action:
– For DW612 enclosure
1. Ensure the power supplies are composed of the same power type.
2. For enclosure type 2, ensure the power supply slots 7~9 is clear.
3. For enclosure type 2 or 3, ensure the power supplies are 2400W.
4. For SD650-N V2, ensure the power supplies are 2400W.
5. For SD650-N V2 400W, ensure the enclosure type is 2 or 3.
6. For SD650-N V2 500W, ensure the enclosure type is 3.
– For DA240 enclosure
1. Ensure all power supplies are 2400W.
– If the event persists, please consult with technical service.
•
180701EA: Zone FFS: Chassis, transition to Non-Critical from OK was asserted.
The fans reside in zone 1 are requested to ramp up to full speed.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112426
User Action:
1. Ensure the room temperature remains at the required level.
2. Ensure the fan modules in fan zone 1 are installed and operating properly.
3. If the event persists, please consult with technical service.
•
180701ED: PSU Policy Lost: Chassis, transition to Non-Critical from OK was asserted.
The configured power policy has been disabled.
.
29
Содержание 7D1J
Страница 4: ...ii ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 8: ...4 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 174: ...170 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 238: ...234 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 242: ...238 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 244: ...240 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 245: ......
Страница 246: ......