Serviceable: Yes
Automatically notify Support: Yes
Alert Category: Critical - Voltage
SNMP Trap ID: 1
CIM Prefix: PLAT CIM ID: 0480
User Action:
Complete the following steps:
1. Reseat the identified compute node.
2. If the specified sensor is system board 12V, ensure PDB is installed correcly and check the XClarity
Controller event log for power-supply-related issues, and resolve those issues.
3. If the specified sensor is system board 3.3V or system board 5V, (trained technician only) replace the
defective node tray.
4. If the problem persists, (trained technician only) replace the PDB or the defective node tray.
•
FQXSPPW0047M: Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted.
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: Yes
Alert Category: Critical - Voltage
SNMP Trap ID: 1
CIM Prefix: PLAT CIM ID: 0494
User Action:
Complete the following steps:
1. Reseat the identified compute node.
2. If the specified sensor is system board 12V, ensure PDB is installed correcly and check the XClarity
Controller event log for power-supply-related issues, and resolve those issues.
3. If the specified sensor is system board 3.3V or system board 5V, (trained technician only) replace the
defective node tray.
4. If the problem persists, (trained technician only) replace the PDB or the defective node tray.
•
FQXSPPW0057J: Sensor [SensorElementName] has transitioned from normal to non-critical state.
This message is for the use case when an implementation has detected a Sensor transitioned to non-
critical from normal.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - Power
SNMP Trap ID: 164
CIM Prefix: PLAT CIM ID: 0520
User Action:
Please check the event log in System Management Module 2 (SMM2) Web GUI.
•
FQXSPPW0061M: Sensor [SensorElementName] has transitioned to critical from a less severe
state.
132
ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference
Содержание 7D1J
Страница 4: ...ii ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 8: ...4 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 174: ...170 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 238: ...234 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 242: ...238 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 244: ...240 ThinkSystem DA240 Enclosure and ThinkSystem SD630 V2 Compute Node Messages and Codes Reference ...
Страница 245: ......
Страница 246: ......