BOP-1K-GL 111315
2-11
CAUTION: DO NOT repeatedly toggle the POWER circuit breaker/switch as this may
damage the unit.
5. Connect the power supply to source power (see PAR. 2.5.2). With no load connected, set
POWER switch to the ON position.
6. Each time the unit is turned on an internal self-test is performed. If the unit passes, it initial-
izes with the power-up settings established in step 1 and the front panel POWER/FAULT/
LIMIT light is green (power good), the DIGITAL CONTROL light is not lit (analog input
enabled) and the VOLTAGE/CURRENT light is green (voltage mode), MASTER/SLAVE light
is green (standalone or master configuration) and the OUTPUT ON light is lit (output
enabled). If the front panel POWER/FAULT/LIMIT light is red, the unit has failed self-test;
contact Kepco for further instructions. If the unit beeps, or the MASTER/SLAVE or VOLT-
AGE/CURRENT light blinks, refer to PAR. 3.8 for troubleshooting.
7. Send the following SCPI commands:
*IDN?
The unit responds with model number and serial number.
FUNC:MODE VOLT
Puts the unit in Voltage Mode.
VOLT:MODE FIX
Allows digital control of the output.
CURR:PROT:LIM xx
xx is the nominal current rating of the unit.
VOLT yy
yy is the nominal voltage rating of the unit.
OUTP ON
Enables the output.
MEAS:VOLT?
Measures output voltage and returns value to host computer.
8. Connect a digital voltmeter (DVM) (resolution and accuracy of 0.01% or better) to the
OUTPS and COMS terminals at the rear panel terminal block.
9. Verify DVM voltage reading matches the nominal voltage of the unit within 0.01% of rated
maximum voltage.
2.4
INSTALLATION
2.4.1
RACK MOUNTING
The unit is shipped with four feet attached to bottom of the unit which must be removed prior to
installation (see Figure 1-2). The BOP is designed to be rack mounted in a standard 19-inch
wide rack using the mounting ears (supplied) attached to the front panel (see Figure 1-2). Allow
a minimum of 1.0 in. (25.4 mm) in front of the unit to permit air intake necessary for proper cool-
ing of the unit.
CAUTION: The rack must provide support at the rear (within 6 inches of
the rear panel). Optional slides can also be used (see PAR. 2.4.2).
2.4.2
SLIDE INSTALLATION
Optional slides are available for rack mounting (see Table 1-5 and Figure 1-2).
Содержание BOP-GL 1KW