BOP-1K-GL 111315
3-9
3.3.6
DETERMINING HOW THE UNIT RESPONDS WHEN OUTPUT IS OFF (LOAD TYPE)
The BOP supports three Load Type selections (see Table 3-3) which determine how the power
supply responds when the output is off: ACTIVE, RESISTIVE and BATTERY. These selections
are designed to provide proper operation with different load types. It is important to note that the
Load Type selection does not affect the settings of the power supply for ON state; it only affects
the main internal reference level and the protection levels during the OFF state. Load type is
selected by performing a Reset Power-up (see PAR. 3.3.2.1) or by using the digital
OUTP:MODE command (see PAR. B.17).
For inductive loads, and especially superconducting magnet type
loads, the inherent offset of the BOP in the OFF state may generate sig-
nificant current in the circuit. A properly rated switch in parallel with a
resistor must be connected between the power supply and the load.
The switch must be open and voltage and current measurements at the
output must read 0V, 0A before removing or installing connections
between BOP and load.
ACTIVE.
Active mode (default setting) is necessary for the power supply to function properly
and safely with inductive loads and constant-current-type active electronic loads. Active mode
can also be used with resistive loads. Table 3-3 indicates how the power supply responds to a
command to go from Output ON to OFF. When the output is disabled, the unit is set to voltage
mode, voltage is set to zero and both current protect and voltage limit are set to maximum.
When the unit is enabled, the pre-existing settings for voltage, current protect and voltage limit
are restored.
For both inductive loads and constant-current-type active electronic
loads when the BOP output is set to OFF, a path is provided for absorb-
ing either the energy accumulated in the reactance of the load during
the ON state, or energy delivered by an electronic load. This prevents
damage to the load and power supply as well as providing safety for
the user. However, In addition to the built-in safety features, constant-
current-type active electronic loads must be adjusted to zero and volt-
age and current measurements at the output must read 0V, minimum
current, before handling the power supply-to-load connections.
RESISTIVE.
This mode, as the name suggests, is useful for resistive loads. Table 3-3 indicates
how the power supply responds to a command to go from Output ON to OFF.
WARNING
WARNING
Содержание BOP-GL 1KW
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 111315 FIGURE 1 1 HIGH POWER BOP GL SERIES POWER SUPPLY...
Страница 36: ...1 16 BOP 1K GL 111315 FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 38: ......
Страница 116: ......
Страница 128: ......
Страница 174: ......