Page 6.2 - 4
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Start-up
6.2.1.1 - v/f characteristic operation
1.
Open control release
deactivate terminal X2A.16
⇒
Inverter state ru.00 = „noP“/„0: no control release“
2.
Selection of the speed range
The required speed range (e.g.: 0..+/- 4000 rpm) is selected in
control type Ud.02.
⇒
Ud.02 control type = 4…7
All data for the adjustment of the controller type (e.g. resolution
of the speed, etc.) see chapter 5.1
Attention: Changing the control type
releases loading of the default para-
meters!
The speed range should be selected
at least 10% higher than the highest
setpoint speed in the application.
3.
Loading the default parameters
Loading the default parameters (KEB factory setting) by
⇒
Fr.01 copy parameter set = - 4
Attention: Pre-adjustments (e.g. func-
tion of the digital inputs) disappear
4.
Selection of the controller configuration
adjust V/f characteristic operation
⇒
cS.00 speed control config. = 0: off
(default v/f – characteristic operation)
Motor data are not necessary for standard v/f - characteristic
operation.
The following parameters must be examined if SMM (sensor-
less motor management for speed stabilization during load)
should not be used:
Frequency when the highest voltage is output:
uF.00 rated frequency
Voltage in [%], which is output at 0Hz:
⇒
uF.01 Boost
If these adjustments for the motor are made correctly continue
to proceed at point 9.
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...