Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 5
7
7.13.1.1 underpotential
"Error! Undervoltage" (E.UP) is triggered if the DC link voltage drops due to brownouts or a generally too weak
power grid. For this error, the automatic restart can be activated.
Suppression of E.UP and no PU at inactive control release
Pn.84 no PU / E.UP deceleration time
Value range: 0 (off) ... 32.00 s; Resolution: 0.01 s; Default value : 0(off)
The following function is activated with this parameter (value <> 0):
With inactive control release E.UP is no ERROR (status word), ru.00 displays nevertheless E.UP
With inactive control release no PU is no ERROR (status word), ru.00 displays nevertheless NO_PU
Other malfunctions (e.g. E.EF, E.dOH) are triggered furthermore
If the control release is activated, E.UP or no PU is triggered after the adjusted time is up, if the condition is still
met (DC link too low or LT_OK signal not active).
If no E.UP or no PU is once activated as ERROR, the status remains until reset.
Reset is only possible at activated control release if the DC link is high enough and/or the signal LT_OK is
active.
If the control release is deactivated, status ERROR is deactivated with a reset.
DC link level to activate the load-shunt
Pn.77 Load-shunt activation voltage
Value range: 0 (off)-1500 V, default value: 0 (off)
Internal lower limit: E.UP-Level (dependent on power unit)
Internal upper limit: E.UP-Reset level - hysteresis (dependent on power unit)
Function:
The function is deactivated with active modulation.
The load-shunt is activated if the modulation is already deactivated (e.g. nop) and the DC link voltage falls
below Pn.77. The status is E.LSF.
E. UP is triggered if the voltage drops below the E.UP level or after 10 s in E.LSF status, if the voltage does
not rise again.
The charging relay time for deactivation of the load-shunt starts as before, if DC bus voltage rises again above
the E.UP reset level.
To ensure a safe operation Pn.77 should be adjusted smaller max. by the hysteresis than the internal upper
limit .
Overview voltage level
Voltage class
E.UP-Level standard
E.UP-Reset level
Hysteresis
230 V
216 V
230 V
5 V
400 V
240 V
300 V
10 V
690 V
360
450 V
15 V
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...