Page 8.1 - 8
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Troubleshooting
Display
COMBIVIS
Value Meaning
E. UP
Error ! underpotential
2
Error: Undervoltage (DC-link circuit). Occurs, if DC-link voltage falls
below the permissible value. Causes:
input voltage too low or unstable
inverter rating too small
voltage losses through wrong cabling
the supply voltage through generator / transformer breaks down at
very short ramps
at F5-G B housing E.UP is also displayed if no communication takes
place between power circuit and control card.
jump factor (Pn.56) too small
if a digital input was programmed as external error input with error
message E.UP (Pn.65).
E.UPh
Error ! Phase failure
3
One phase of the input voltage is missing (ripple-detection)
Warning Messages
A.buS
Warning ! Watchdog
93
Watchdog for communication between operator - PC or operator
- inverter has responded. The response to this warning can be
programmed.
A.dOH
Warning ! drive overheat
96
The motor temperature has exceeded an adjustable warning level.
The switch off time is started. The response to this warning can be
programmed. This warning can be generated only with a special
power circuit.
A. EF
Warning ! ERROR external
fault
90
This warning is triggered via an external input. The response to this
warning can be programmed.
A.ndOH
no ABN.STOP drive overheat
91
The motor temperature is again below the adjusted warning level.
The switch off time is stopped.
A.nOH
no ABN.STOP overheat pow.
mod.
88
The heat sink temperature is again below the adjusted warning level.
A.nOHI
no ABN.STOP overheat
internal
92
The temperature in the interior of the inverter is again below the
warning threshold.
A.nOL
no ABN.STOP overload
98
Warning: no more overload, OL counter has reached 0 %, warning
„overload" can be reset.
A.nOL2
no ABN.STOP overload 2
101
The cooling time after “Warning! Overload during standstill" has
elapsed. The warning message can be reset.
A. OH
Warning ! overheat pow.mod.
89
This warning is output when the defined level is exceeded. Furthermore
the response to this warning can be programmed.
A.OH2
Warning ! motor protection
97
Warning: electronic motor protective relay has tripped. The response
to this warning can be programmed.
A.OHI
Warning ! overheat internal
87
The temperature in the interior of the inverter is above the permissible
level. The switch off time was started. The programmed response to
this warning message is executed.
A. OL
Warning ! overload
99
A level between 0 and 100 % of the load counter can be adjusted.
The warning is output on exceeding this level. The response to this
warning can be programmed.
A.OL2
Warning ! overload 2
100
The warning is output when the standstill continuous current is
exceeded (see technical data and overload characteristics). The
response to this warning can be programmed. The warning message
can only be reset after the cooling time has elapsed and A.nOL2 is
displayed.
further on next side
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...