Troubleshooting
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 8.1 - 7
8
Display
COMBIVIS
Value Meaning
E.OL2
Error ! overload 2
19
Occurs if the standstill constant current is exceeded (see technical
data and overload characteristics). The error can only be reset if the
cooling time has elapsed and E.nOL2 is displayed.
E.OP
Error ! overvoltage
1
Voltage in the DC-link circuit too high. Occurs if the DC-link voltage
exceeds the permissible value. Causes:
poor controller adjustment (overshooting)
input voltage too high
interference voltages at the input
deceleration ramp too short
braking resistor defective or too small
E.OS
Error ! over speed
58
The speed is outside the defined limits. (can also occur on exceeding
of the absolute speed referring to EMF = EMF wrong (servo drives).
E.PFC
Error ! PFC
33
Error in the power factor control.
E.PrF
Error ! prot. rot. for.
46
The drive has driven onto the right limit switch. Programmed response
“Error, restart after reset” (see chapter 6.7 “Response to errors or
warning messages”).
E.Prr
Error ! prot. rot. rev.
47
The drive has driven onto the left limit switch. Programmed response
“Error, restart after reset” (see chapter 6.7 “Response to errors or
warning messages”).
E. Pu
Error ! power unit
12
Error: General power circuit fault
E.Puci
Error ! power circuit unknown
49
Error: During the initialization the power circuit could not be recognized
or was identified as invalid.
E.Puch
Error ! power unit changed
50
Error: Power circuit identification was changed; the error can be
reset by writing on SY.03 at valid power circuit. If the value displayed
in SY.03 is written, only the power-circuit dependent parameters
are reinitialized. If any other value is written, then the default set is
loaded. A power-on-reset is necessary on some systems after writing
of SY.03.
E.PUCO
Error ! power unit
communication
22
Error: Parameter value could not be written to the power circuit.
Acknowledgement from LT <> OK
E.PUIN
Error ! power circuit coding
14
Error: Software version for power circuit and control card are different.
Error cannot be reset (only at F5-G B-housing)
E.SbuS
Error ! bus synchron
23
Sychronization over sercos-bus not possible. Programmed response
“Error, restart after reset”.
E.SCL
ERROR! speed controller
limit
25
Speed controller limit reached
E.SEt
Error ! set
39
It has been attempted to select a locked parameter set. Programmed
response “Error, restart after reset”.
E.SLF
Error ! Software limit switch
forward
44
The target position lies outside of the limit defined with the right
software limit switch. Programmed response “Error, restart after
reset”.
E.SLr
Error ! software limit switch
reverse
45
The target position lies outside of the limit defined with the left software
limit switch. Programmed response “Error, restart after reset”.
further on next side
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...