Page 7.5 - 24
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Motor data and controller adjustments of the asynchronous motor
fn = rated frequency
nn = rated speed
Selection of the rated switching frequency of the inverter:
The output frequency should not exceed 1/10 of the switching frequency.
Thus the following applies:
switching fre-
quency
max. output frequency
output speed (for pole-pair number = 2)
2 kHz
200Hz
6000 rpm
4 kHz
400Hz
12000 rpm
8 kHz
800Hz
24000 rpm
12 kHz
----
---
16 kHz
1600Hz
48000 rpm
Note: That a spindle e.g. with leakage inductance dr.07 = 1.4 mH and output frequency of 800 Hz (24000 rpm)
can be driven in practice also with 4kHz should not be considered for the dimensioning of the inverter.
Double modulation output:
An additional voltage vector can be output for 8 and16 kHz. The current controller is calculated only all 12 µs,
but the transformation angle is changed by 62.5 µs
(dS.18 bit 6 = on ).
Switching off the hardware current limit (HCL):
If the motor model is activated, HCL generally should be deactivated via uf.15 = 0 =off.
Identification of the equivalent circuit data:
•
Main inductance:
There can be problems at measurement of the main inductance in lower speed range and when reaching
the target speed.
Lower speed range:
Measurement of the main inductance is started with a value for the inductance which is calculated from
the motor data. The lower speed range must be passed through speedy because the mode of calculation
can only be estimated and additionally the motor data of the manufacturers are problematically . For this
the additional ramp in dS.21 and dS.22 make sense.
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...