Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 7
7
7.13.1.5
Inverter over temperature
Heat sink overtemperature
The heat sink temperature acquisition protects the power module from thermal overload. The temperature at
which the inverter switches off with error message "8: ERROR! Overtemperature" (E.OH) depends on the po-
wer circuit (generally 90°C).
After cooling period the status changes from "Error! Overtemperature" to "36: Heat sink temperature normal
again" (E.nOH) and is therefore resettable.
A level between 0° C and 90 °C, when the pre-warning is triggered can be adjusted with Pn.11 "OH warning
level". The response to the warning message is set with Pn.10 "warning OH stop. mode".
Internal overtemperature
The interior temperature monitoring protects the inverter against malfunctions caused by too high temperature
in the interior of the inverter. Upon exceeding a unit-specific temperature the interior fan is activated. If the tem
-
perature is still too high after about 10 min., the disconnecting time set with Pn.17 "internal overtemperature
disconnecting time" (0...120s) starts.
With the start of the disconnecting time, switching condition "11: Warning internal overheating" is met and the
response to the warning message set in Pn.16 "warning OHI stop. mode" is executed.
After expiration of the disconnecting time, "6: ERROR! Overtemperature interior" (E.OHI) is triggered.
When the interior temperature has dropped again, the inverter state changes again to "7: interior temperature
back to normal" (E.nOHI). The error can now be reset.
7.13.1.6
External fault
With Pn.04 "Input selection external error", one or more digital inputs can be programmed which can trigger the
error "31: ERROR! External input" (E.EF).
With Pn.03 "Response to external error"
, the response of the inverter to the digital input is defined. With
Pn.65/
bit 1 "2:Pn.04 = E.UP", the function of Pn.04 can be changed and the triggering of an error via a digital input
can be deactivated.
7.13.1.7
Bus error
The inverter contains two watchdogs that monitor the communication between an external bus, operator, and
inverter control.
With parameter
Pn.05 "Response to E.bus", the response to a watchdog error is defined. Dependent on the
chosen adjustment, either "Error! Watchdog" (E.buS) or "Warning! Watchdog error" (A.buS), is issued or a war-
ning message via a digital output is generated.
Watchdog time (Pn.06)
This watchdog monitors the communication at the operator interface. With activated watchdog, the response
set in Pn.05 is triggered after expiration of an adjustable time (0.01...40 s) without incoming telegrams.
The function is deactivated by setting the value "0: off".
HSP5 Watchdog time (SY.09)
The HSP5 watchdog function monitors the communication of the HSP5 interface (control card - operator; or
control card - PC). After expiration of an adjustable time (0.01...10 s) without incoming telegrams, the response
adjusted in Pn.05 is triggered. Value „0: off“ deactivates the function.
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...