Page 7.13 - 6
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Protective functions
7.13.1.2 Overvoltage
"Error! Overvoltage" is triggered if the DC link voltage increases beyond the overvoltage level due to energy
recovery in regenerative operation.
7.13.1.3 overcurrent
The "Error! Overcurrent" (E.OC) is trigger when the "OC-tripping current" (see technical data in the instruction
manual power circuit F5) is exceeded.
If this error occurs permanently, either the connected motor (short circuit or ground fault) or the inverter itself
is defective.
The "maximum short time current limit" is below the overcurrent limit. If it is exceeded, the hardware current
limit can be triggered with uF.15. The response of this function is not considered an error or malfunction, and
the corresponding switching conditions are not set. If the function is active, the status "80:hardware current
limitation active" (HCL) is displayed.
For current regulated drives, this function should be deactivated since it may have negative effects for the motor
model calculation and the behaviour of the drive.
7.13.1.4 overload
The inverter-overload protection is a function that triggers an error for which, however, a pre-warning can be
generated.
There are two overload protection functions: one for the range of standstill and low frequencies (overload at
standstill/ OL2) and one for the remaining frequency range (overload/ OL).
With Pn.09 "Overload warning level" a value between 0...100 % can be adjusted, when the "Warning! Overload"
or the "Warning! Overload during standstill", is set. The response to the overload warning is set with Pn.08
"warning OL stop. mode".
Overload in the standstill (OL2)
The implementation of the function "19: Overload during standstill" is described in chapter 2.1.9 "Overload
protection in the lower speed range". The motor current is guided via a PT1 link with a time constant of 280 ms.
If this delayed current exceeds the OL2 limit, "Error! Overload during standstill" (E.OL2) is triggered. If the dela-
yed current decreases to 0 again, the inverter enters the status "20: Overload during standstill fixed" (E.nOL2).
The error can now be reset.
Overload (OL)
The implementation of the general overload protection is described in chapter 2.1.8 "Overload characteristics".
If the 100% load factor of the inverter is exceeded by 5 %, the internal overload counter starts to count forward.
If the load factor falls below 100 %, the counter counts backward. The current counter content can be read in
parameter ru.39. Upon reaching 100 % the inverter switches off with error message "E.OL" and the counter
counts backward. If it reaches 0 %, the status changes to E.nOL and the error can be reset.
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...