![INVT GD350-004G-4 Скачать руководство пользователя страница 99](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703099.webp)
Goodrive350 series high-performance multifunction VFD
Basic operation guidelines
-90-
Function
code
Name
Description
Default
value
P05.48
Corresponding setting of
upper limit frequency of
HDIB
-300.0%
–300.0%
100.0%
P05.49
HDIB frequency input filter
time
0.000s
–10.000s
0.030s
P05.50
AI1 input signal type
0
–1
0: Voltage type
1: Current type
0
5.5.10 Analog output
The VFD carries one analog output terminal (0
–10V/0–20mA) and one high-speed pulse output
terminal. Analog output signals can be filtered separately, and the proportional relation can be
adjusted by setting the max. value, min. value, and the percentage of their corresponding output.
Analog output signal can output motor speed, output frequency, output current, motor torque and
motor power at a certain proportion.
0
1
2
3
.
.
.
.
.
.
19
20
P06.14
P06.16
AO1
HDO
P06.17
P06.18
P06.19
P06.20
P06.27
P06.28
P06.29
P06.30
P06.21
P06.31
(Default value is 0)
(Default value is 0)
P06.00
(HDO output type)
0
1
P06.00
0: Open collector high-speed
pulse output
1: Open-collector output
Analog output curve setting
Analog output selection
Analog output filter
AO output relationship description:
(The min. value and max. value of the output correspond to 0.% and 100.00% of the pulse or analog
default output. The actual output voltage or pulse frequency corresponds to the actual percentage,
which can be through function codes.)
Setting
Function
Description
0
Running frequency
0
–Max. output frequency
1
Set frequency
0
–Max. output frequency
2
Ramp reference frequency
0
–Max. output frequency
3
Running speed
0
–Synchronous speed corresponding to max. output
frequency