Goodrive350 series high-performance multifunction VFD
Function parameter list
-205-
Function
code
Name
Description
Default
value
Modify
P11.15
Speed deviation
detection time
Used to set the speed deviation detection time.
Note: Speed deviation protection is invalid
when P11.15 is set to 0.0.
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running
Fault output
Setting range: 0.0
–10.0s
2.0s
○
P11.16
Automatic
frequency-reducti
on during voltage
drop
0
–1
0: Invalid
1: Valid
0
○
P11.17
Proportional
coefficient of
voltage regulator
during
undervoltage stall
This parameter is used to set the proportional
coefficient of the bus voltage regulator during
undervoltage stall.
Setting range: 0
–1000
100
○
P11.18
Integral
coefficient of
voltage regulator
during
undervoltage stall
This parameter is used to set the integral
coefficient of the bus voltage regulator during
undervoltage stall.
Setting range: 0
–1000
40
○
P11.19
Proportional
coefficient of
current regulator
during
undervoltage stall
This parameter is used to set the proportional
coefficient of the active current regulator during
undervoltage stall.
Setting range: 0
–1000
25
○
P11.20
Integral
coefficient of
current regulator
during
undervoltage stall
This parameter is used to set the integral
coefficient of the active current regulator during
undervoltage stall.
Setting range: 0
–2000
150
○
P11.21
Proportional
coefficient of
voltage regulator
This parameter is used to set the proportional
coefficient of the bus voltage regulator during
overvoltage stall.
60
○