Goodrive350 series high-performance multifunction VFD
Function parameter list
-161-
Function
code
Name
Description
Default
value
Modify
factor of motor 1 properly to eliminate such phenomenon.
Setting range of P04.10: 0
–100
Setting range of P04.11: 0
–100
Setting range of P04.12: 0.00Hz
–P00.03 (Max.
output frequency)
P04.12
Oscillation
control threshold
of motor 1
30.00Hz
○
P04.13
V/F curve setting
of motor 2
This parameter defines the V/F curve of motor 2 of
the VFD to meet various load characteristic
requirements.
0: Straight V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customize V/F (V/F separation)
0
◎
P04.14
Torque boost of
motor 2
Note:
Refer to the parameter description of
P04.01 and P04.02.
Setting range of P04.14: 0.0%: (automatic) 0.1%
–
10.0%
Setting range of 0.0%
–50.0% (relative to rated
frequency of motor 2)
0.0%
○
P04.15
Torque boost
cut-off of motor 2
20.0%
○
P04.16
V/F frequency
point 1 of motor 2
Note:
Refer to the parameter description of
P04.03
–P04.08
Setting range of P04.16: 0.00Hz
–P04.18
Setting range of P04.17:0.0%
–110.0% (rated
voltage of motor 2)
Setting range of P04.18: P04.16
–P04.20
Setting range of P04.19: 0.0%
–110.0% (rated
voltage of motor 2)
Setting range of P04.20: P04.18
–P12.02 (rated
frequency of asynchronous motor 2) or P04.18
–
P12.16 (rated frequency of synchronous motor 2)
Setting range of P04.21: 0.0%
–110.0% (of the
rated voltage of motor 2)
0.00Hz
○
P04.17
V/F voltage point
1 of motor 2
00.0%
○
P04.18
V/F frequency
point 2 of motor 2
0.00Hz
○
P04.19
V/F voltage point
2 of motor 2
0.0%
○
P04.20
V/F frequency
point 3 of motor 2
0.00Hz
○
P04.21
V/F voltage point
3 of motor 2
0.0%
○
P04.22
V/F slip
compensation
gain of motor 2
This parameter is used to compensate for the
motor rotating speed change caused by load
change in the SVPWM mode, and thus improve
the rigidity of the mechanical characteristics of the
motor. You need to calculate the rated slip
frequency of the motor as follows:
0.0%
○