![INVT GD350-004G-4 Скачать руководство пользователя страница 220](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703220.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-211-
Function
code
Name
Description
Default
value
Modify
P12.17
Number of pole
pairs of
synchronous
motor 2
1
–128
2
◎
P12.18
Rated voltage of
synchronous
motor 2
0
–1200V
Depends
on model
◎
P12.19
Rated voltage of
synchronous
motor 2
0.8
–6000.0A
Depends
on model
◎
P12.20
Stator resistance
of synchronous
motor 2
0.001
–65.535Ω
Depends
on model
○
P12.21
Direct-axis
inductance of
synchronous
motor 2
0.01
–655.35mH
Depends
on model
○
P12.22
Quadrature-axis
inductance of
synchronous
motor 2
0.01
–655.35mH
Depends
on model
○
P12.23
Counter-emf
constant of
synchronous
motor 2
0
–10000V
300
○
P12.24
Reserved
/
/
/
P12.25
Reserved
/
/
/
P12.26
Overload
protection of
motor 2
0: No protection
1: Common motor (with low-speed compensation)
2: Frequency-variable motor (without low-speed
compensation)
2
◎
P12.27
Overload
protection
coefficient of
motor 2
Motor overload multiples M = Iout/(In×K)
In is rated motor current, lout is VFD output
current, K is motor overload protection coefficient.
The smaller the K, the larger the value of M, the
easier the protection.
When M=116%, protection is performed after
motor overload last for 1 hour; when M=150%,
100.0%
○