![INVT GD350-004G-4 Скачать руководство пользователя страница 261](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703261.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-252-
Function
code
Name
Description
Default
value
Modify
Setting range: 0
–65535
P23.11
Speed loop
differential gain
0.00
–10.00s
0.00s
○
P23.12
Proportional
coefficient of
high-frequency
current loop
In the FVC (P00.00=3), when the frequency is
lower than the current-loop high-frequency
switching threshold (P23.14), the current-loop PI
parameters are P23.09 and P23.10; and when the
frequency is higher than the current-loop
high-frequency switching threshold, the
current-loop PI parameters are P23.12 and
P23.13.
Setting range of P23.12: 0
–65535
Setting range of P23.13: 0
–65535
Setting range of P23.14: 0.0
–100.0% (relative to
max. frequency)
1000
○
P23.13
Integral
coefficient of
high-frequency
current loop
1000
○
P23.14
High-frequency
switchover
threshold of
current loop
100.0%
○
P23.15
–
P23.19
Reserved
/
/
/
P24
––
Encoder of motor 2
Function
code
Name
Description
Default
value
Modify
P24.00
Encoder type
display
0: Incremental encoder
1: Resolver-type encoder
2: Sin/Cos encoder
3: Endat absolute encoder
0
●
P24.01
Encoder pulse
number
Number of pulses generated when the encoder
revolves for one circle.
Setting range: 0
–60000
1024
◎
P24.02 Encoder direction
0x000
–0x111
Ones: AB direction
0: Forward
1: Reverse
Tens: Z pulse direction (reserved)
0: Forward
1: Reverse
Hundreds: CD/UVW pole signal direction
0: Forward
1: Reverse
0x000
◎
P24.03 Detection time of 0.0
–10.0s
2.0s
○