Goodrive350 series high-performance multifunction VFD
Technical data
-379-
must be installed and operated by specialized personnel when applied to the first environment
Note:
The EMC standard IEC/EN 61800-3 no longer restricts the power distribution of VFDs, but it
specifies their use, installation, and commissioning. Specialized personnel or organizations must
have the necessary skills (including the EMC-related knowledge) for installing and/or performing
commissioning on the electrical drive systems.
C3: Rated voltage lower than 1000 V, applied to the second environment. They cannot be applied to
the first environment.
C4: Rated voltage higher than 1000 V, or rated current higher or equal to 400 A, applied to complex
systems in the second environment.
B.6.1 VFD category C2
The induction disturbance limit meets the following stipulations:
1. Select an optional EMC filter according to Appendix D Optional peripheral accessories and install
it following the description in the EMC filter manual.
2. Select the motor and control cables according to the description in the manual.
3. Install the VFD according to the description in the manual.
4. For the maximum length of the motor cable, see section "EMC compatibility and motor cable
B.6.2 VFD category C3
The anti-interference performance of the VFD meets the requirements of the second environment in
the IEC/EN 61800-3 standard.
The induction disturbance limit meets the following stipulations:
1. Select an optional EMC filter according to Appendix D Optional peripheral accessories and install
it following the description in the EMC filter manual.
2. Select the motor and control cables according to the description in the manual.
3. Install the VFD according to the description in the manual.
4. For the maximum length of the motor cable, see section "EMC compatibility and motor cable
VFDs of C3 category cannot be applied to civilian low-voltage common grids.
When applied to such grids, the VFDs may generate radio frequency
electromagnetic interference.