Goodrive350 series high-performance multifunction VFD
Basic operation guidelines
-116-
time (Ti) and prolong derivative time (Td) to stabilize control as fast as possible.
Before adjustment
After adjustment
Response
Time t
Control long-term vibration:
If the cycle of periodic vibration is longer than the set value of integral
time (Ti), it indicates the integral action is too strong, prolong the integral time (Ti) to control vibration.
Before adjustment
After adjustment
Time t
Response
Control short-term vibration
: If the vibration cycle is short is almost the same with the set value of
derivative time (Td), it indicates derivative action is too strong, shorten the derivative time (Td) to
control vibration. When derivative time (Td) is set to 0.00 (namely no derivative control), and there is
no way to control vibration, decrease the proportional gain.
Before adjustment
After adjustment
Response
Time t
Related parameter list:
Function
code
Name
Description
Default
value
P09.00
PID reference source
0: Set by P09.01
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Multi-step
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet
communication
0