![INVT GD350-004G-4 Скачать руководство пользователя страница 193](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703193.webp)
Goodrive350 series high-performance multifunction VFD
Function parameter list
-184-
Function
code
Name
Description
Default
value
Modify
(C2-Er)
65: Communication timeout of the card at slot 3
(C3-Er)
66: EtherCAT communication fault (E-CAT)
67: Bacnet communication fault (E-BAC)
68: DeviceNet communication fault (E-DEV)
69: CAN slave fault in master/slave
synchronization (S-Err)
70: EC PT100 detected overheating (OtE1)
71: EC PT1000 detected overheating (OtE2)
72: EtherNet/IP communication timeout (E-EIP)
73: No upgrade bootload (E-PAO)
74: AI1 disconnected (E-AI1)
75: AI2 disconnected (E-AI2)
76: AI3 disconnected (E-AI3)
P07.33
Running
frequency at
present fault
0.00Hz
–P00.03
0.00Hz
●
P07.34
Ramp reference
frequency at
present fault
0.00Hz
–P00.03
0.00Hz
●
P07.35
Output voltage at
present fault
0
–1200V
0V
●
P07.36
Output current at
present fault
0.0
–6300.0A
0.0A
●
P07.37
Bus voltage at
present fault
0.0
–2000.0V
0.0V
●
P07.38
Max. temperature
at present fault
-20.0
–120.0°C
0.0°C
●
P07.39
Input terminal
status at present
fault
0x0000
–0xFFFF
0x0000
●
P07.40
Output terminal
status at present
fault
0x0000
–0xFFFF
0x0000
●
P07.41
Running
frequency at last
fault
0.00Hz
–P00.03
0.00Hz
●