![INVT GD350-004G-4 Скачать руководство пользователя страница 140](http://html1.mh-extra.com/html/invt/gd350-004g-4/gd350-004g-4_operation-manual_2085703140.webp)
Goodrive350 series high-performance multifunction VFD
Basic operation guidelines
-131-
Function
code
Name
Description
Default
value
2nd-last fault
P07.52
Output current at
2nd-last fault
0.0
–6300.0A
0.0A
P07.53
Bus voltage at
2nd-last fault
0.0
–2000.0V
0.0V
P07.54
Max. temperature at
2nd-last fault
-20.0
–120.0°C
0.0°C
P07.55
Input terminal status
at 2nd-last fault
0x0000
–0xFFFF
0x0000
P07.56
Output terminal
status at 2nd-last
fault
0x0000
–0xFFFF
0x0000
5.5.20 Tension control solutions
In many fields of industrial production, precise tension control is needed to maintain a constant output
tension of the drive equipment, in order to improve the quality of the products. In the winding and
unwinding of some industries such as paper processing, printing and dyeing, packing, wire and cable
manufacturing, textile, fiber, optic cable, leather, metal foil material processing and so on, tension
needs to keep constant.
The VFD controls the tension by regulating the motor output torque or speed. There are three modes
to control the tension: speed mode, open-loop torque mode and closed-loop torque mode.
5.5.20.1 Typical tension control applications for winding/unwinding
Unwinding in speed mode
Traction
Winding in torque mode
V
Tension feedback